ILO Home
Volver a la página de entrada
Site map | Contact us English | Français

Base de datos CISDOC

ID (ISN) del documento56941
Número CIS 91-1925
ISSN - Título de la serie 0002-8894 - American Industrial Hygiene Association Journal
Año 1991
Número de serie
Autor(es) Puskar M.A., Szopinski F.G., Hecker L.H.
Título Development and validation of a protocol for field validation of passive dosimeters for ethylene oxide excursion limit monitoring
Información bibliográfica Apr.1991, Vol.52, No.4, p.145-150. Illus. 10 ref.
Resumen The protocol uses a field exposure chamber with concurrent sampling using Tedlar air-sampling bags. The bags are analysed after sampling by gas chromatography with flame ionisation detection (GC-FID). The chamber design allows all dosimeters to be exposed at the same time in the field. The sampling and analysis procedure determines the actual concentration of ethylene oxide (EtO) present during the dosimeter's exposure, and estimates if EtO concentrations vary from point to point in the dosimeter array during the exposure. In chamber operation, the accuracy of the standard generator used to calibrate the GC-FID was independently verified in the field by the standard additions method. The study reports the sampling biases and estimates the stability of collected EtO samples in Tedlar bags.
Descriptores (primarios) compuestos epoxi; óxido de etileno; aparatos de exposición experimental; pruebas en el puesto de trabajo; análisis químico; aparatos de muestreo; toma de muestras y análisis; toma de muestras del aire; dosimetría
Descriptores (secundarios) límites de confianza; detección por ionización; cromatografía en fase gaseosa; descripción del procedimiento
Tipo de documento D - Artículos periódicos
País / Estado o ProvinciaEstados Unidos
Tema(s) Sustancias tóxicas y peligrosas
Broad subject area(s) Riesgos químicos
Navegación por categoria(s) Ethers
Ethylene oxide