Autor(es) Biegelmeier G.
Título Currents passing through the body, limits of contact voltage and protective measures
Título original Körperströme, Berührungsspannungsgrenzen und Schutzmassnahmen [en alemán]
Información bibliográfica Ausgabe B, 1975, Vol.27, No.17, p.461-464. Illus. 10 ref.
Resumen After an introductory section on cardiac function, the excitation phase and ventricular fibrillation, the author refers to animal experiments and accident investigations in a study of the minimum duration of exposure to an electric current, the fibrillation threshold, and the current intensity ranges. Conclusions relating to the hazard ranges and the efficacy of high-sensitivity differential circuit breakers. In extreme conditions (brief duration of exposure in the critical T-wave phase, resistance of the fault circuit less than 500Ω), the differential circuit breaker cannot prevent a fatal outcome. Differential circuit breakers should therefore not be used without a protective conductor.
Descriptores (primarios) corriente eléctrica; corrientes umbrales; protección contra los fallos de voltaje
Descriptores (secundarios) fibrilación ventricular; efectos biológicos; toma a neutro