ILO Home
Volver a la página de entrada
Site map | Contact us English | Français

Base de datos CISDOC

ID (ISN) del documento21581
Número CIS 74-1508
ISSN - Título de la serie Quarterly Safety Summary of the British Chemical Industry Safety Council
Año 1973
Número de serie
Título Fire prevention and protection - Carbon dioxide in fire extinguisher systems.
Información bibliográfica Apr.-June 1973, Vol.44, No.174, p.10. 1 ref.
Resumen One of the hazards associated with the use of CO2 in fire extinguishers is the production of very high electrical charges during release, which may ignite explosive mixtures if such are present. Measurements showed that small solid particles of CO2 are produced containing static electricity with voltages of 10-20 kV and potential spark energies easily capable of igniting the lower paraffins. Nitrogen is preferred to CO2 in fire-fighting systems since it does not produce solid particles when releasing the pressure and the amount of static electricity is less pronounced, but the use of solid CO2 generators is suggested as a safe way to replace air by a non-explosive mixture in a reaction vessel.
Descriptores (primarios) lucha contra el fuego; riesgos de explosión; electricidad estática; dióxido de carbono
Descriptores (secundarios) reemplazamiento; nitrógeno
Tipo de documento -
Tema(s) Incendios, explosiones
Broad subject area(s)
Navegación por categoria(s) Inorganic substances
Carbon dioxide
Explosions
Incendios
Electricidad