Document ID (ISN) | 55709 |
CIS number |
91-560 |
Year |
1990 |
Convention or series no. |
Undersökningsrapport 1990:8
|
Author(s) |
Andersson B., Andersson K., Sundgren M., Sundell J., Mattsson K.O., Zingmark P.A. |
Title |
Reentrainment of air pollutants in rotary heat exchangers |
Original title |
Återföring av luftföroreningar i roterande värmeväxlare [in Swedish] |
Bibliographic information |
Arbetsmiljöinstitutet, Förlagstjänst, 171 84 Solna, Sweden, 1990. 19p. Illus. 11 ref. |
Abstract |
Six exchangers, installed in office buildings in the northern part of Sweden, were included in this study. Formaldehyde in the indoor air was used as a monitor pollutant and was sampled at 4 positions around the rotor, before and after passage of the rotor, in both the exhaust and supply air streams. Sampling of homogeneous air in the ducts was performed simultaneously with 2,4-dinitrophenylhydrazine-coated glass fibre filters. The analysis of formaldehyde was made by high performance liquid chromatography. The reentrainment of formaldehyde was 1-9%. |
Descriptors (primary) |
heat exchangers; atmospheric pollution; ventilation |
Descriptors (secondary) |
report; high-pressure liquid chromatography; monitoring for air contamination; exhaust ventilation |
Document type |
E - Books, reports, proceedings |
Country / State or Province | Sweden |
Subject(s) |
Heating, ventilation and climate
|
Broad subject area(s) |
Chemical safety
|
Browse category(ies) |
Air pollution Environmental pollution Ventilation
|