Author(s) Caplan K.J., Knutson G.W.
Title Influence of room air supply on laboratory hoods
Bibliographic information Oct. 1982, Vol.43, No.10, p.738-746. Illus. 3 ref.
Abstract The effect of room air supply system on laboratory fume hood performance was investigated using a previously developed test. The test measures the concentration of tracer gas in the breathing zone of the worker when the tracer, mixed with air, is released at known rates at various positions within the hood. The terminal velocity of supply air jets is as important as the hood face velocity in its effect on performance. Terminal velocity of jets should be <1/2 to 2/3 the face velocity. Data for wall grilles, ceiling diffusers and perforated ceiling panels are presented.
Descriptors (primary) exhaust hoods; aerodynamics; laboratory work
Descriptors (secondary) air movement; ventilation design; laboratory equipment; evaluation of equipment
Document type D - Periodical articles
Subject(s) Heating, ventilation and climate
Broad subject area(s)
Browse category(ies) Ventilation