ILO Home
Go to the home page
Site map | Contact us Français | Español

CISDOC database

Document ID (ISN)37989
CIS number 82-989
Year 1982
Convention or series no. SIS Report 1982:5
Author(s) Waskaas M.
Title Electrical fields in high-voltage installations - Results of measurements under overhead electricity lines, in distribution installations and power generating stations
Original title Elektriske felt i høyspenningsanlegg - En kartlegging av elektriske felt under kraftledninger, i fordelingsanlegg of i kraftstasjoner [in Norwegian]
Bibliographic information Statens institutt for strålehygiene, Østerndalen 25, 1345 Østerås, Norway, 1982. 57p. Illus. 20 ref.
Abstract Sections cover: physics of electrical and magnetic fields; instruments and methods for measuring field intensity; results. These show that electrical field intensities, measured 1.8m above ground under overhead lines, depend on the voltage level, the height of the lines above ground and the type of pylon. Field intensity may be as high as 6kV/m in the case of a 420kV line 11.5m above ground (the natural atmospheric electrical field intensity being only 0.13kV/m). Intensity falls exponentially with increasing line height. Measurements at 1.8m above the ground in 420 and 300kV substations showed maximum intensities of 11kV/m and 6.4kV/m at a distance of 2.5m from the disconnecting switches.
Descriptors (primary) work near electric lines; electric power generation; electric fields; high voltage
Descriptors (secondary) substations; Norway; report; magnetic fields; overhead electric lines; field strength measurement; electric power distribution
Document type E - Books, reports, proceedings
Subject(s) Radiation
Broad subject area(s)
Browse category(ies) Power generation and distribution
Electromagnetic fields
Electricity