Título |
Movement under emergency lighting: the effect of illuminance |
Información bibliográfica |
1985, Vol.17, No.2, p.51-71. Illus. 12 ref. |
Resumen |
An investigation was carried out in a large open-plan office with the aim of identifying the illuminance necessary for rapid, safe movement under emergency lighting conditions. At a mean illuminance of 0.2lx, the test subjects had difficulty in moving quickly over the escape route. Optimum illuminance for quick and orderly evacuation was established at 1lx. It seems that the prsent emergency lighting criterion of 0.2lx used in the United Kingdom should be revised and the 1lx standard adopted. |
Descriptores (primarios) |
oficinas ajardinadas; trabajo de oficina; iluminación de seguridad; duración de la evacuación; recorridos de evacuación |
Descriptores (secundarios) |
Reino Unido; norma; comentario de ley; socorro y evacuación |
Tipo de documento |
F - Notas informativas, directrices prácticas, normas |
Tema(s) |
Iluminación, color, visión
|
Broad subject area(s) |
|
Navegación por categoria(s) |
Office work Lighting and colour First aid and emergency organization
|