Número CIS 82-989
Año 1982
Número de serie SIS Report 1982:5
Autor(es) Waskaas M.
Título Electrical fields in high-voltage installations - Results of measurements under overhead electricity lines, in distribution installations and power generating stations
Título original Elektriske felt i høyspenningsanlegg - En kartlegging av elektriske felt under kraftledninger, i fordelingsanlegg of i kraftstasjoner [en noruego]
Información bibliográfica Statens institutt for strålehygiene, Østerndalen 25, 1345 Østerås, Norway, 1982. 57p. Illus. 20 ref.
Resumen Sections cover: physics of electrical and magnetic fields; instruments and methods for measuring field intensity; results. These show that electrical field intensities, measured 1.8m above ground under overhead lines, depend on the voltage level, the height of the lines above ground and the type of pylon. Field intensity may be as high as 6kV/m in the case of a 420kV line 11.5m above ground (the natural atmospheric electrical field intensity being only 0.13kV/m). Intensity falls exponentially with increasing line height. Measurements at 1.8m above the ground in 420 and 300kV substations showed maximum intensities of 11kV/m and 6.4kV/m at a distance of 2.5m from the disconnecting switches.
Descriptores (primarios) trabajo cerca de las líneas eléctricas; producción de energía eléctrica; campos eléctricos; alta tensión
Descriptores (secundarios) subestaciones; Noruega; informe; campos magnéticos; líneas eléctricas aéreas; medida de la intensidad de campo; distribución de la energía eléctrica
Tipo de documento E - Libros, informes, actas
Tema(s) Radiaciones
Broad subject area(s)
Navegación por categoria(s) Power generation and distribution
Electromagnetic fields
Electricidad